SCPTdeviceControlMode

Overview:

Device control mode..  Normal default operating device control mode. 

This configuration property sets the device control mode to be used for the normal operating mode when a remote network pressure or flow sensor is not bound to a controller and the internal speed, pressure or flow feedback signal is used by the controller.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 238
Obsolete: no
Size: 1
Programmatic Name: SCPTdeviceControlMode
Default: DCM_SPEED_CONST
Neuron C Type:
SNVT_dev_c_mode
Formats:

SCPTdeviceControlMode:  text("%m")

Used by:

SFPTpumpController